| Description
General information
The current protections type of RFI 421 type are intended to
be used like a multifunc-tional relay protection, automatics and remote
control units for middle voltage feeders and also like back-up protections
for low voltage sides of the power transformers. For line protection,
the device can be used in networks with grounded, low resis-tance grounded,
isolated or compensated neutral point. It is suitable for radial sys-tems
with single-end infeed or open ring systems.
RFI 421 devices can be used as a single
unit as well as a part of ROCON hierarchy structure. The ROCON hierarchy
structure comprises two levels – local controllers (RFI 401) and work
station. The data transfer is done trough an industrial local network.
The dialog with the relay can be done locally by means
of an operational interface (situated on the relay’s front panel) or remotely
– by means of PC connected and MMI (Man Machine Interface) service program.
Event Recorder and Disturbance Recorder
functions are integrated into the device. Communication with SCADA or
substation controller equipment (work station) is available. The connection
can be done via serial interfaces through the choice of data cable, modem,
or optical fibers.
RFI 421 includes
up to 4 selectable setting groups. Transition from one setting group to
another can be done during exploitation of the device.
locally - trough
the front device's keypad
remotely - by running
MMI-service program or by command from work station (SCADA)
via dedicated binary
inputs.
Relay protection functions overview
ANSI 50, 51 - Definite time delay overcurrent
protection
| |
Non-directional time
delay over-current protection with definite time;
Possibility for acceleration before or after Autoreclosing;
Possibility for acceleration in case of remote or manual circuit
breaker (CB) closing.
|
ANSI 50, 51 - Instantaneous overcurrent protection
| |
Non-directional instantaneous
(or with time delay) over-current protection;
Three possibilities for the operational principle – non selective
protection for cable line, non-selective protection, overhead line
(blocked when autoreclosing is OFF) or selective protection;
Possibility for acceleration before or after autoreclosing;
Possibility for acceleration in case of remote or manual CB closing;
Possibilities for blocking of the function from an external signal
received by dedicated binary inputs. |
ANSI 51 - Inverse time delay overcurrent protection
| |
Non-directional inverse
time delay overcurrent protection
Selectable time delay characteristic according to IEC and ANSI standards:
According IEC: Inverse time, Very Inverse, Extremely Inverse,
Long Inverse, RI Inverse
According ANSI: Long Inverse, Moderately Inverse, Very Inverse,
Extremely Inverse, Isquared T
|
ANSI 50N, 51N - Overcurrent ground fault protection
| |
Non-directional ground-fault
protection with definite time delay;
Up to 3 stages and possibility for switching ON or OFF for each
stage separately;
Possibility for acceleration at autoreclosing for each stage separately;
Possibility for acceleration in case of remote or manual circuit
breaker (CB) clos-ing for each stage separately. |
ANSI 51N - Inverse time delay ground fault protection
| |
Non-directional protection;
Selectable time delay characteristic according to IEC and ANSI standards:
According IEC: Inverse time, Very Inverse, Extremely Inverse,
Long Inverse, RI Inverse
According ANSI: Long Inverse, Moderately Inverse, Very Inverse,
Extremely Inverse, Isquared T |
ANSI 46 - Negative sequence overcurrent protection
| |
Evaluation of negative
sequence component of the currents – ANSI 46;
In line protection, the negative-sequence protection permits detection
on the high side of high-resistance phase-to-phase faults and phase-to-earth
faults that are on the low side of a transformer. This provides
backup protection for high-resistance faults beyond the transformer.
To detect the unbalanced load, the ratio negative-sequence current/rated
(nominal) current is evaluated;
A measured current element for the negative sequence current - I2;
Timer activated at current measuring element pick-ups;
Possibilities for blocking of the NSOC from an external signal received
by dedicated binary input.
|
ANSI 49 - Thermal overload protection
| |
Uses a thermal model
of the line based on its heating and cooling time constants and
an exponential law of alteration;
Monitors the temperature state through the relative temperature
which is connected with the squared current of the line;
In case of overload the protection picks-up with a delay which depends
on the degree of overload;
The protection has two stages providing trip and pre-trip alarm
outputs;
Possibilities for blocking of the TOL from an external signal received
by dedicated binary input.
|
Unbalance overcurrent protection
| |
Protect the feeder in
case of current unbalance;
Monitors the maximum difference between the effective values of
the three phase currents;
Switches off automatically if the maximum phase current exceeds
the threshold setting;
Except for the unbalanced voltage supply, the protection picks up
at the interterm faults and at double-phase short circuits near
to the neutral. |
AUTORECLOSING
| |
Autoreclosing
function acc. ANSI 79AR;
Up to 6 shots;
The device is equipped with an operation counter for counting the
rapid and delayed autoreclosings (AR) - counting the one-shot AR,
two-shots AR, three shots AR and four-, five-, six-shots AR. Also
two special counters are implemented into the device - for counting
the successfully done and unsuccessfully done AR.
Starting condition:
At the circuit
breaker and control switch position discrepancy• at the circuit
breaker and control switch position discrepancy
At tripping
command: from internal protections; from external protections -
by binary inputs; from internal or external protections.
|
Circuit breaker life time monitoring
| |
Visualization
of the circuit breaker’s phase life time;
Signalization of CB run out of resource;
Possibility for describing of the CB life time curves;
Possibility for editing the CB’s life time value for each phase.
The RFI 401 device has 4 selectable setting groups including all
protection and automation functions. Commutation between the separate
groups can be achieved locally, remotely or via dedicated binary
inputs.
|
Data aquisition & remote control functions
Remote measurement
| |
Measures, processes and
archives information about instant and integral values for the analogue
quantities of the protected feeder;
Calculates the average “rms” values of the voltage for each second
and sends them through the local network to the connected PC work
station (WS)
Sends the data to the WS for maximal registered values
The measured analogue values are displayed continuously on the LCD
of the device. |
Remote control
| |
Възможност за телеуправление
на прекъсвач и разединители (шинни, линейни, земен нож)
Получава, обработва и предава за изпълнение приетите от ОС (или Диспечерския
пункт) телекоманди
Следи и контролира изпълнението на командите за телевключване и телеизключване
Възможност за подаване на телекоманди от бутони на устройството |
Remote signalization
| |
RFI
421 receives processes and archives the following information:
Primary equipment
status change
Warning and
alarm signalization received from external devices for relay protection
and automation – operation of load shedding relays and auxiliary power
supply failure relays, for example
Pick-up and
drop-off of the voltage relays of the internal relay protection functions
Trip commands
sent to the CB from internal relay protection functions
Alarm signalization
related to the remote control function operation (CB or disconnectors)
– failure in execution of the remote control command, attempt for
not permitted command issuing and etc.
Signalizations for controlled values limit overreaching
The device time synchronizations (by front panel or remotely)
Changing of the working parameters of the device (new configuration,
new re-lay protection settings and new parameters for remote control
functions)
Clearing of the data from Event Recorder or Disturbance recorder.
|
Event Recorder function
Disturbance Recorder function
| |
For each of the event included
into the Event recorder can be set to initiate additional more detailed
oscillographic data collection. The period of the data collection
consist of two intervals pre-history duration and during the fault.
These records consist of all measured and calculated analogue values
(wave-form), binary inputs and outputs and processing points. The
values recorded are measured with maximal sampling frequency of the
device. The records from the Disturbance recorder function can be
transferred to the connected PC running MMI service program. On the
Work station PC (SCADA-system) the information recorded can be added
to the archive displayed in graphical way and used for detailed analysis
of the primary events and the behavior of the relay protections and
primary equipment. |
Working in SCADA-system
| |
The device can be connected
to Work Station in SCADA-system by means of local network. The network
is based on RS485 or fiber optic – the respective interface connector
is used. The communication protocol is IEC 60870-5-103 / IEC 61850.
The device’s data acquisition and remote control functions are performed
by means of work station – measuring, signaling, remote control
(opening or closing command to the circuit breaker, disconnecttors,
earthing switch).
Additionally by work station facilities the device can be configured
its settings parameters, can be read and corrected and all stored
into unit’s memory data can be archived. Also all data stored by
means of “Disturbance recorder” and “Event recorder” functions can
be transferred and archived into WS for farther analysis. |
Human Machine Interface (HMI)
Man Machine Interface - MMI
Technical data
POWER
SUPPLY |
|
| Rated
voltage, Un |
110 / 220 V DC/AC (-20% ... +20%) |
DC
supply interruption |
According
to IEC 60255-11:
0,1 s / 100 % at 110/220 V
0,01 s / 100 % at 24 V |
| Burden |
7
W |
| ANALOG
INPUTS |
|
| Frequency |
|
| -rated values fn |
50 Hz (option 60 Hz) |
| -operational range |
46 ... 52 Hz |
| Current
inputs |
4 pcs. |
| Rated current, In |
5 А / 1 А |
| Consumption |
<0,1 VA at In = 5A |
Thermal current withstand
(acc. IEC 60255-6, IEC 60255-3) |
continuous - 10.In,
for 1 s – 100.In
for 10 ms - 250.In |
| Range of precise operation |
(0,1 ... 40).In |
| BINARY
INPUTS |
|
| Total
number |
8
pcs. |
| Auxiliary
power supply |
|
-
Rated voltage |
110/220
V DC/AC |
| -
Operational range |
-20
% ... +20 % at Un |
| Burden
in each input circuit |
0,75
W at 220 V DC
0,4 W at 110 V DC |
BINARY
OUTPUTS |
|
| Total number |
8 pcs. |
| Electromechanical relays with NO/NC contacts |
8 А max
250 V AC / DC max
2 000 VA < 10 ms operation time |
| CONSTRUCTION |
|
| External part Metal welded
box |
|
| Flush mounting |
|
| Dimensions |
245 mm x 185 mm x 72 mm |
| Weight |
2,5 kg |
| Protection degree (acc. IEC
60529) |
IP52 (front panel) |
| Surface mounting |
|
| Dimensions |
301 mm x 206 mm x 71 mm |
| Weight |
3,5 kg |
| Protection degree (acc. IEC
60529) |
IP52 (front panel) |
| INTERFACES |
|
| Communication
protocols: |
IEC
60870-5-103, IEC 60870-5-NEO |
| RS485
electrical |
38,4
kbit/s max |
| RS232
current loop / optical head |
9,6
kbit/s |
| ELECTRICAL
TESTS |
|
| Insulation
Tests |
IEC 60255-5, class 3 |
| High Voltage Test |
2
kV; 50 Hz; 1 min |
| Impulse Voltage Test |
5
kV; 1,2 / 50 ms; 0,5 J |
|
Insulation Resistance Test |
>100
MW ; 500 V DC |
| |
|
| ELECTROMAGNETIC
COMPATIBILITY (EMC) |
|
| EMC
– disturbance immunity |
|
| High frequency disturbance |
IEC
60255-22-1; EN 61000-4-12, class 3 |
| Electrostatic
Discharge |
IIEC
60255-22-2
EN 61000-4-2, class 4 |
| Radio-frequency Electromagnetic Field: |
IEC
60255-22-3; EN 61000-4-3, class 3 |
| Fast Transients |
IEC
60255-22-4,
EN 61000-4-4, class 4 |
| Surge
immunity |
IEC
60255-22-5; EN 61000-4-5, class 3 |
| Conductive
radio disturbances |
IEC
60255-22-6; EN 61000-4-6, class 3 |
| Power frequency magnetic field |
EN
61000-4-8, class 4 |
| |
|
| EMC
- emissions |
IEC
CISPR 11, class A |
| |
|
| MECHANICAL
TESTS |
|
| During operation |
|
| Vibration |
IEC
60255-21-1, class 1; IEC 60068-2-6 |
| Shocks |
IEC
60255-21-2, class 1; IEC 60068-2-27 |
| Seismic tests |
IEC
60255-21-3, class 1, IEC 60068-3-3 |
| During
transport (with standard package) |
|
| Vibrations |
IEC
60255-21-1, class 1; IEC 60068-2-6 |
| Shocks |
IEC
60255-21-2, class 1; IEC 60068-2-27 |
| Bump |
IEC
60068-2-29 |
| AMBIENT
CONDITIONS |
|
| During
transportation and storage |
IEC 60068-2-1;
IEC 60068-2-2 |
| –
During transportation and storage |
-40
... +70 ° C |
| –
During exploitation |
-5
...+55 ° C |
|
|